Description |
Part Number |
Price |
|
Universal Signal Conditioner |
USC701-2001 |
$520.00 |
|
Access Module for USC701 |
AM702 |
$320.00 |
|
Computer Adapter for USC701 |
COA703 |
$320.00 |
|
*Access Module and Computer Adapter are free if purchased with 5 items of Universal Signal Conditioner |
||
|
Size: |
80W x 70H x 110D mm. |
|
Housing material: |
Polycarbonate, aluminium. |
|
Mounting: |
DIN-Rail, gear plate. |
|
Termination: |
Plug in screw terminals. |
|
Weight: |
0.3 kg. |
|
Protection class: |
IP40 (IP65 Enclosure opt.) |
|
Electromagnetic compatibility: |
Compiles with AS/NZS |
|
Operating temp. range: |
0...+60ºC |
|
Storage temp. range: |
-20...+70ºC |
|
Isolation: |
1000Vac r.m.s. /1500Vdc |
|
Temperature effect: |
0.02% per ºC |
|
Measurement Linearity: |
+ - 0.01% of range. |
|
Measurement Accuracy: |
typ + - 0.05%dc, + - 0.2%ac input range. |
|
Resolution: |
+ - 0.0025% of range. |
| Update time: | 16.6 msec minimum. |
| Filtering/averaging: | programmable. |
| Power Supply -1: | 80 - 300Vdc / 80 - 280Vac |
| Power Supply -2: | 10 - 60Vdc / 16 - 42Vac |
| Power requirement: | 4VA |
|
Voltage source: |
3V to 18V @ 50 mA max |
|
Current source: |
1 x 100µA external 1 x 100µA internal |
|
+, -, *, /, absolute value, minimum, maximum, scaling, taring; plus logical functions. |
|
|
Minimum and maximum hold, multiple 100 point linearisation and alarm functions. |
|
|
Number of channels: |
either 2 single ended or one differential pair. |
|
Input resistance: |
15k to 4.4Ohmns (v), 83Ohmns (l) |
|
Voltage dc: |
+ - (400, 100, 30, 10, 4.5, 1Vdc) |
|
mV dc: |
+ - (300, 100, 30mV) |
|
Current dc: |
+ - (75, 30, 10, 1mA) |
|
Voltage ac: |
300, 75, 25, 7, 3Vac (25 - 70 Hz) |
|
mV ac: |
700, 250, 75, 20mV (25 - 70 Hz) |
|
Current ac: |
50, 20, 7, 0.7mA (25 - 70 Hz) |
|
Resistance: |
30, 10, 3, 1, 0.3kOhmns (2, 3 or 4 wire) |
|
Potentiometer: |
100 Ohmns minimum |
|
RTD (Pt100) |
Linearised to + - 0.1ºC 850ºC + - 0.2ºC, 600ºC + - 0.1ºC |
|
Thermocouple: |
linearised to + - 0.1ºC types: B, E, J, K, N, R, S, T accuracy depends on Type and range. cold junction comp + - 1ºC + - 0.05º/ºC Up/downscale burn-out by external resistor |
|
Contacts: |
N/O 8A/250Vac resistive, 3.5A/250Vac Inductive. |
|
Action: |
Programmable: direct, reverse, window, latch. |
| Dead Band: | Programmable. |
|
Delays: on/off |
up to 1 hour. |
|
Contact isolation: |
2kV. |
|
Number of channels: |
2 |
|
Range: |
+/- 30V |
|
Input resistance: |
20k |
|
Trigger level: |
0 to 28V adjustable |
|
Programmable ranges Frequency: |
1pulse/hr to 5kHZ resolution: 0.002% accuracy: + - 0.005% |
|
Mains Frequency inducer: |
ranges as required e.g. 48-52Hz |
|
Phase: |
+ - 180º (for frequencies to 100Hz) |
|
Other Functions: |
hold, reset, enable |
|
Open-collector: |
30V, 20mA |
|
Current dc: |
0 to 22 mA ( 20V drive) |
|
Voltage dc: |
0 to 20V range (20mA drive) |
|
Accuracy: |
0.1% of range |
|
Linearity: |
0.05% of range |
|
Response time: |
50msec |
|
Output load change effect: |
less than 0.2% |
|
Physical: |
RS485, CAN (factory set) |
|
Protocol: |
Profibus, Devicenet, Modbus |
|
USC701 - Xa Xb 0 1 |
Xa: Supply 1 = 80-300Vdc / 80-280Vac 50/60Hz 2 = 10V - 60Vdc / 16 - 42Vac 50/60Hz
Xb: Fieldbus 0 = None 1 = Modbus 2 = Devicenet 3 = Profibus |