ISAS

.

.

Member of
Open
DeviceNet
Vendors
Assoc.

DeviceNet

Developer of RTD
temperature sensor
for DeviceNet

Enter DeviceNet
Te
mperature
Sensor

 

New Products
Specials

 


A.P.C.S. UNIVERSAL SIGNAL CONDITIONER (v1) USC701


General Specifications



Pricing

Description

Part Number

Price

Universal Signal Conditioner

USC701-2001

$520.00

Access Module for USC701

AM702

$320.00

Computer Adapter for USC701

COA703

$320.00

*Access Module and Computer Adapter are free if purchased

with 5 items of Universal Signal Conditioner

 

General Specifications

Size:

80W x 70H x 110D mm.

Housing material:

Polycarbonate, aluminium.

Mounting:

DIN-Rail, gear plate.

Termination:

Plug in screw terminals.

Weight:

0.3 kg.

Protection class:

IP40 (IP65 Enclosure opt.)

Electromagnetic

compatibility:

Compiles with AS/NZS

Operating temp. range:

0...+60ºC

Storage temp. range:

-20...+70ºC

Isolation:

1000Vac r.m.s. /1500Vdc

Temperature effect:

0.02% per ºC

Measurement Linearity:

+ - 0.01% of range.

Measurement Accuracy:

typ + - 0.05%dc, + - 0.2%ac

input range.

Resolution:

+ - 0.0025% of range.

Update time: 16.6 msec minimum.
Filtering/averaging: programmable.
Power Supply -1: 80 - 300Vdc / 80 - 280Vac
Power Supply -2: 10 - 60Vdc / 16 - 42Vac
Power requirement: 4VA

Auxiliary Excitation Output

Voltage source:

3V to 18V @ 50 mA max

Current source:

1 x 100µA external

1 x 100µA internal

Mathematical Functions

+, -, *, /, absolute value, minimum, maximum,

scaling, taring; plus logical functions.

Application Functions

Minimum and maximum hold, multiple 100 point

linearisation and alarm functions.

Analog Inputs

Number of channels:

either 2 single ended or one

differential pair.

Input resistance:

15k to 4.4Ohmns (v),

83Ohmns (l)

Programmable ranges

Voltage dc:

+ - (400, 100, 30, 10, 4.5, 1Vdc)

mV dc:

+ - (300, 100, 30mV)

Current dc:

+ - (75, 30, 10, 1mA)

Voltage ac:

300, 75, 25, 7, 3Vac (25 - 70 Hz)

mV ac:

700, 250, 75, 20mV (25 - 70 Hz)

Current ac:

50, 20, 7, 0.7mA (25 - 70 Hz)

Resistance:

30, 10, 3, 1, 0.3kOhmns

(2, 3 or 4 wire)

Potentiometer:

100 Ohmns minimum

RTD (Pt100)

Linearised to + - 0.1ºC

850ºC + - 0.2ºC, 600ºC + - 0.1ºC

Thermocouple:

linearised to + - 0.1ºC

types: B, E, J, K, N, R, S, T

accuracy depends on Type and

range.

cold junction comp + - 1ºC

+ - 0.05º/ºC

Up/downscale burn-out by

external resistor

Two Relay Outputs

Contacts:

N/O 8A/250Vac resistive,

3.5A/250Vac Inductive.

Action:

Programmable: direct, reverse,

window, latch.

Dead Band: Programmable.

Delays: on/off

up to 1 hour.

Contact isolation:

2kV.

Digital Inputs

Number of channels:

2

Range:

+/- 30V

Input resistance:

20k

Trigger level:

0 to 28V adjustable

Programmable ranges

Frequency:

1pulse/hr to 5kHZ

resolution: 0.002%

accuracy: + - 0.005%

Mains Frequency

inducer:

ranges as required e.g. 48-52Hz

Phase:

+ - 180º (for frequencies to 100Hz)

Other Functions:

hold, reset, enable

Isolated Analog/Open Collector Output

Open-collector:

30V, 20mA

Current dc:

0 to 22 mA ( 20V drive)

Voltage dc:

0 to 20V range (20mA drive)

Accuracy:

0.1% of range

Linearity:

0.05% of range

Response time:

50msec

Output load change

effect:

less than 0.2%

Isolated Digital Output

Physical:

RS485, CAN (factory set)

Protocol:

Profibus, Devicenet, Modbus

USC Type No. Designation

USC701 - Xa Xb 0 1

Xa: Supply

1 = 80-300Vdc / 80-280Vac 50/60Hz

2 = 10V - 60Vdc / 16 - 42Vac 50/60Hz

 

Xb: Fieldbus

0 = None

1 = Modbus

2 = Devicenet

3 = Profibus

 

Back To Top